Sign in
Please login to continue to your account.
The typical application for the Brooks Interlinkerator BLINK-240 is a block of units where Brooks’s 240V smoke/heat alarm system is installed in the individual units and a commercial fire system is installed in the common areas such as hallways car parks, etc.
An alarm inside the unit, will cause the smoke/heat alarms to sound, the interlinkerator remains non-active. If the alarm occurs in the common area, the commercial system will trigger the Brooks Interlinkerator which supplies an isolated 9VDC to the interconnect bus of the smoke/heat alarms and will continuously flash the “EVACUATE” sign. The Brooks Interlinkerator provides the occupant a way to distinguish between alarms inside their own units and fire alarms in the common areas.
BLINK-12 may be used in similar applications by replacing 240V smoke / heat alarm system by a single zone residential panel BARFS-1 which uses 12V smoke or heat alarms.